Hurst Euro Series Boiler

THREE-PASS SCOTCH MARINE DESIGN

LOW PROFILE, WET BACK CONSTRUCTION

Available in 8 Models from 100 - 2000 BHP 

Steam Pressures to 15-300 PSI 

Hot Water Section I and Section IV 

Wetback design eliminates refractory rear door & baffles between flue gas passes

  • Natural Gas
  • Oil
  • Combination
  • Steam
  • Hot Water

Standard Features

  • Boiler is of the three-pass, scotch type, built and stamped in accordance with the requirements of the ASME Code, and listed by the National Board of Boilers and Pressure Vessel Inspectors.
  • Large combustion chamber with low heat release for complete combustion. Smoke box is rear-mounted with slip-on stack connector.
  • Access to fireside is accomplished with hinged and davited front and rear doors. Flame observation ports are located on front and rear.
  • Openings for vessel cleanout and inspection of waterside are provided with 3" x 4" hand holes, and 12" x 16" manway access.
  • Insulated with 2" high density mineral wool, lagged with 22 gauge grip jacketing, baked on finish to resist chipping and fading.
  • Firetubes are rolled and beaded on power boilers, expanded and flared on low pressure boilers.
  • Supports include lifting lugs securely welded to the top of shell; structural steel support legs on skids support the boiler so that special foundations are not required.

Standard Steam Trim

  • Operating & high limit pressure control
  • Modulating pressure control (when applicable)
  • Water column with gauge glass, combination low water cut-off & pump control
  • Probe Aux, L.W.C.O. Steam pressure gauge, syphon & test cock
  • Water column drain valve
  • Safety relief valve(s) per ASME Code

Standard Water Trim

  • Operating & high limit temperature control
  • Modulating temperature control (when applicable)
  • Probe type low water cut-off control
  • Combination pressure & temperature gauge
  • Hot water return baffle for shock resistance
  • Safety relief valve(s) per ASME Code

Boiler Design

Three-Pass "Scotch Marine" Firetube design with stress relieving "Wetback" construction. Pressure designs for steam are 15-300 psi. 100-600 hp. 250 psi. max. for 700-1500 hp. and 200 psi. max. for 1800-2000 hp. Hot Water pressures models are from 30-160 psi. High pressure, high temperature Section I hot water boilers available. Factory assembled with trim, tested, ASME code, UL, and CSD-1 standards.

Steam Model Trim

Safety relief valve, operating pressure control, high limit pressure control with manual reset, steam pressure gauge with syphon, combination pump control and low water cut-off with gauge glass assembly and drain valve, auxiliary low water cut-off with manual reset.

Hot Water Model Trim

Safety relief valve, operating temperature control, high limit temperature control with manual reset, combination pressure & temperature gauge, low water cut-off control with manual reset. BURNER: Matched UL listed "forced draft" power burners with factory prepiped, wired and tested fuel configurations for natural gas, propane (LP) gas, No. 2 (diesel) oil, or combination of both gas/oil.

Hurst Euro Series Boiler

Licenses & Certifications

ASME R

ASME R

Repair and alteration of boilers and pressure vessels in compliance with ASME standards ensuring safety and integrity.

ASME U

ASME U

Manufacture and assemble pressure vessels with ASME Boiler and Pressure Vessel Code (BPVC) Section VIII Division 1 standards.

ASME S

ASME S

Design, fabrication, and assembly of power boilers intended for producing steam or other vapor for power generation purposes.

Board C1A License 0081463 and C21 License 0083749

Nevada Contractor

Nevada State Contractors Board C1A License 0081463 and C21 License 0083749.

Top